Universal flameproof box type USO 2 – ****

Description

Uniwersalna skrzynka ognioszczelna typu USO 2
Uniwersalna skrzynka ognioszczelna typu USO 2

Flame-proof junction boxes type USO 2 – **** They are suitable for safe use in underground mines in workings classified as “a”, “b” or “c” of methane explosion hazard and “A” or “B” class of coal dust explosion hazard.
Universal flameproof boxes type USO 2 – **** are intended for connecting shielded mining power cables made of thermoplastics and mining tire cables with rated voltages not exceeding 3.6 / 6 kV in all workings of non-methane and methane mining plants.

The series of USO boxes:

  • USO 2-6352 – box with an insulation level of 6000 V, with 350 A current clamps, pass-through,
  • USO 2-6353 – box with an insulation level of 6000 V, with 350 A current terminals, straight-through or manifold, (3 cable inlet sockets),
  • USO 2-1402 – box with insulation level max. 1100 V, with 400 A current terminals, through hole,
  • USO 2-1403 – box with insulation level max. 1100 V, with 400 A current terminals, straight-through or branching, (3 cable inlet sockets),
  • USO 2-1404 – box with insulation level max. 1100 V, with 400 A current terminals, straight-through or branching, (4 cable inlet sockets),

For type boxes USO 2-1402, USO 2-1403, USO 2-1404 it is possible to use three types of covers: cover without sight glasses or cover with  four sight glasses WZA-70 or three type sight glasses WZA-90.

 

Rated data

Box typeUSO 2-6352
USO 2-6353
USO 2-1402
USO 2-1403
USO 2-1404
Nominal voltage Un
Rated current. In
max 6000 V
350 A
max 1100 V
400 A
Short circuit current Iz
Short circuit time tz
10 kA
0.1 s
10 kA
0.1 s
Dimensions:
Ø
H
~325 mm
~215 mm
~325 mm
~215 mm
Number of inletsUSO 2-6352 – 2 inlets
USO 2-6353 – 3 inlets
USO 2-1402 – 2 inlets
USO 2-1403 – 3 inlets
USO 2-1404 – 4 inlets
Type of inlets,
type of drain plug
WKp-1, WKp-2, WKp-3, WKp-4, Z-WKpKDB 05ATEX148UI M2 Ex d I MbII 2G Ex d IIC Gb
Drain reduction typeR-WMg-*OBAC 09ATEX012UI M2 Ex d I
Type of cable entriesWMg KDB 05ATEX395UI M2 Ex d I MbII 2G Ex d IIIC Db IP65
Possible combinations:
-lived strength
– control wires
– grounding conductors
– force veins screens
– general screens
max 3 wires/phase, 150 mm2
max 12 wires, max 4 mm2
max 70 mm2
into the housing
into the housing
max 2 wires/phase, 185 mm2
max 12 wires, max 4 mm2
max 95 mm2
into the housing
into the housing
Working temperaturefrom -10oC to +40oC
Work locationany
Total weightabout 70 kg
Sight glassesFlameproof sight glasses type WZ
FTZÚ 07ATEX0246U
I M 2 Ex d I

Comments:
– Weight shown without cable entries
– Each gully seat may be plugged with an approved gully plug
– USO-1402, USO-1403, USO-1404 boxes can be fitted with approved sight glasses on the front plate

 

The box, as a flameproof casing, which is the basis for the series of types of USO boxes, is made in the form of a steel tube cylinder. Four support sleeves are welded on the outside of the box, used to fix or suspend the box.

Depending on the version of the box (version 1, version 2 or version 3), it has 2, 3 or 4 cable inlet sockets. Cable glands type WKp-1, WKp-2, WKp-3, WKp-4 can be mounted to the cable glands..  Depending on the needs, individual inlets can be closed with plugs Z-WKp or the reduction of the R-WMg inlets.

In the center of the box there are two earthing clamps for earthing general screens of cables or wires. On the outside of the box, there is one earthing terminal for earthing the box.

The upper closure of the box is a flameproof cover with a flameproof cylindrical gap. The cover is closed by turning it through an angle of 15 o and completely locking it by means of a toothed key cooperating with a rack attached to one of the catches of the box cover.

Certificate

Universal flameproof boxes type USO 2 – **** have an EC examination certificate: OBAC 09ATEX266X z dnia 20.10.2009r. which is supplemented by Appendix No. 1 of30.07.2012r. issued by the Center for Testing, Attestation and  Certification of OBAC Sp. z o. o. in Gliwice.

The basic requirements of safety and health protection were implemented by meeting the requirements of the following standards:

  • PN-EN 60079-0:2009
  • PN-EN 60079-1:2010

The universal flameproof boxes type USO 2 – **** are marked with:

 

OBAC 09ATEX266X
I M2 Ex d I Mb
1461

 

Download the catalog card:

Universal flameproof box type USO 2

SELECTED PRODUCTS
flagi programu unijnego funduszu